How do I make this wiring inside cabinet safer? (Pic) Planned maintenance scheduled April 17/18, 2019 at 00:00UTC (8:00pm US/Eastern) Announcing the arrival of Valued Associate #679: Cesar Manara Unicorn Meta Zoo #1: Why another podcast?How do I get power into my kitchen cabinet?Can I install junction boxes in a closet, and if so, what kind of box?Converting 120V undercabinet lighting to 12V strip lightingHow is ground wire handled on 240V outlet?Replacing pendant lights and have a question on all the ceiling box wiresWiring Transition from Inside of wall to Outside of Wall for hard-wired applianceWhat is the proper way to bring this wire up to code and add an outlet?How to: Electrical Wiring Distance & Voltage Dropwiring - is this feeding other circuits or all switches?Would connecting an ungrounded cable to a new grounded cable in a box violate code?
Is it fair for a professor to grade us on the possession of past papers?
How to convince students of the implication truth values?
First console to have temporary backward compatibility
Why are the trig functions versine, haversine, exsecant, etc, rarely used in modern mathematics?
Denied boarding although I have proper visa and documentation. To whom should I make a complaint?
8 Prisoners wearing hats
Why aren't air breathing engines used as small first stages
old style "caution" boxes
Is there a kind of relay only consumes power when switching?
Is it a good idea to use CNN to classify 1D signal?
Circuit to "zoom in" on mV fluctuations of a DC signal?
How to compare two different files line by line in unix?
Why are there no cargo aircraft with "flying wing" design?
What do you call the main part of a joke?
また usage in a dictionary
If a VARCHAR(MAX) column is included in an index, is the entire value always stored in the index page(s)?
What is homebrew?
Using audio cues to encourage good posture
Do jazz musicians improvise on the parent scale in addition to the chord-scales?
Do I really need recursive chmod to restrict access to a folder?
How to tell that you are a giant?
Is there any way for the UK Prime Minister to make a motion directly dependent on Government confidence?
Is "Reachable Object" really an NP-complete problem?
What are the out-of-universe reasons for the references to Toby Maguire-era Spider-Man in ITSV
How do I make this wiring inside cabinet safer? (Pic)
Planned maintenance scheduled April 17/18, 2019 at 00:00UTC (8:00pm US/Eastern)
Announcing the arrival of Valued Associate #679: Cesar Manara
Unicorn Meta Zoo #1: Why another podcast?How do I get power into my kitchen cabinet?Can I install junction boxes in a closet, and if so, what kind of box?Converting 120V undercabinet lighting to 12V strip lightingHow is ground wire handled on 240V outlet?Replacing pendant lights and have a question on all the ceiling box wiresWiring Transition from Inside of wall to Outside of Wall for hard-wired applianceWhat is the proper way to bring this wire up to code and add an outlet?How to: Electrical Wiring Distance & Voltage Dropwiring - is this feeding other circuits or all switches?Would connecting an ungrounded cable to a new grounded cable in a box violate code?
.everyoneloves__top-leaderboard:empty,.everyoneloves__mid-leaderboard:empty,.everyoneloves__bot-mid-leaderboard:empty margin-bottom:0;
tl;dr: How do I make this wiring meet code, or at least safer?
The pic below is inside one of my kitchen cabinets. Once upon a time the stove was located below these cabinets, and that wire must have run to an exhaust fan (note the metal vent in the pic). The stove had been moved to another spot by the time I bought the house, but the wire is still in the cabinet and still live.
When I bought the house the wire (old 2-wire NM, no ground) ran to a light fixture on the underside of the cabinet, but there was no junction box at all. Just exposed pigtails inside the cabinet. I'd like to improve things here, so what can I do, short of running a brand new wire with a ground through the wall? I figure putting the pigtails in an actual junction box would be a good place to start.
I plan on staying in the house for a few more years, so I'm more concerned with safety than exactly meeting code.
wiring
New contributor
add a comment |
tl;dr: How do I make this wiring meet code, or at least safer?
The pic below is inside one of my kitchen cabinets. Once upon a time the stove was located below these cabinets, and that wire must have run to an exhaust fan (note the metal vent in the pic). The stove had been moved to another spot by the time I bought the house, but the wire is still in the cabinet and still live.
When I bought the house the wire (old 2-wire NM, no ground) ran to a light fixture on the underside of the cabinet, but there was no junction box at all. Just exposed pigtails inside the cabinet. I'd like to improve things here, so what can I do, short of running a brand new wire with a ground through the wall? I figure putting the pigtails in an actual junction box would be a good place to start.
I plan on staying in the house for a few more years, so I'm more concerned with safety than exactly meeting code.
wiring
New contributor
1
Is your goal to just leave those wires in the cabinet unused, but in a safe manner - or would you like to utilize them for the light fixture again?
– PhilippNagel
9 hours ago
1
@PhilippNagel I'd like to put the light fixture back, but it's not absolutely critical.
– BradDaBug
9 hours ago
add a comment |
tl;dr: How do I make this wiring meet code, or at least safer?
The pic below is inside one of my kitchen cabinets. Once upon a time the stove was located below these cabinets, and that wire must have run to an exhaust fan (note the metal vent in the pic). The stove had been moved to another spot by the time I bought the house, but the wire is still in the cabinet and still live.
When I bought the house the wire (old 2-wire NM, no ground) ran to a light fixture on the underside of the cabinet, but there was no junction box at all. Just exposed pigtails inside the cabinet. I'd like to improve things here, so what can I do, short of running a brand new wire with a ground through the wall? I figure putting the pigtails in an actual junction box would be a good place to start.
I plan on staying in the house for a few more years, so I'm more concerned with safety than exactly meeting code.
wiring
New contributor
tl;dr: How do I make this wiring meet code, or at least safer?
The pic below is inside one of my kitchen cabinets. Once upon a time the stove was located below these cabinets, and that wire must have run to an exhaust fan (note the metal vent in the pic). The stove had been moved to another spot by the time I bought the house, but the wire is still in the cabinet and still live.
When I bought the house the wire (old 2-wire NM, no ground) ran to a light fixture on the underside of the cabinet, but there was no junction box at all. Just exposed pigtails inside the cabinet. I'd like to improve things here, so what can I do, short of running a brand new wire with a ground through the wall? I figure putting the pigtails in an actual junction box would be a good place to start.
I plan on staying in the house for a few more years, so I'm more concerned with safety than exactly meeting code.
wiring
wiring
New contributor
New contributor
New contributor
asked 11 hours ago
BradDaBugBradDaBug
1161
1161
New contributor
New contributor
1
Is your goal to just leave those wires in the cabinet unused, but in a safe manner - or would you like to utilize them for the light fixture again?
– PhilippNagel
9 hours ago
1
@PhilippNagel I'd like to put the light fixture back, but it's not absolutely critical.
– BradDaBug
9 hours ago
add a comment |
1
Is your goal to just leave those wires in the cabinet unused, but in a safe manner - or would you like to utilize them for the light fixture again?
– PhilippNagel
9 hours ago
1
@PhilippNagel I'd like to put the light fixture back, but it's not absolutely critical.
– BradDaBug
9 hours ago
1
1
Is your goal to just leave those wires in the cabinet unused, but in a safe manner - or would you like to utilize them for the light fixture again?
– PhilippNagel
9 hours ago
Is your goal to just leave those wires in the cabinet unused, but in a safe manner - or would you like to utilize them for the light fixture again?
– PhilippNagel
9 hours ago
1
1
@PhilippNagel I'd like to put the light fixture back, but it's not absolutely critical.
– BradDaBug
9 hours ago
@PhilippNagel I'd like to put the light fixture back, but it's not absolutely critical.
– BradDaBug
9 hours ago
add a comment |
4 Answers
4
active
oldest
votes
There is nothing you can do with old wiring that doesn't meet code that will make it meet code. Old NM cable with no ground may have been "grandfathered" into an existing building, so long as you don't alter it. But that would not apply here because the WAY it was done was never per code.
Do you really need a circuit there? I would just find out where it comes from and disconnect it there, then pull it out. If you DO want another circuit there, you can attach new NM cable with a ground to the end of this before pulling it out, then get an "old work box" that can be mounted into the wall properly. An old work box is designed to go into a cut-out in the wall, then has "molly bolt" type fasteners that turn behind the wall and snug up against the back of it to hold the box in place (make sure you put the wire through the KO first!). Once the wire is in there, you can put in a receptacle for a light, fan etc.
2
If it's stapled anywhere it probably won't pull.
– J...
5 hours ago
True, but given that the original installer didn't seem to have any regard for doing things right, it's likely not stapled anywhere either!
– J. Raefield
4 hours ago
3
Whomever moved the stove and removed the old fixture made a mess, but the wire is probably original and fastened if it is.
– J...
4 hours ago
add a comment |
You may want to find what the local code says about such and follow it. I think just putting it "properly" in a metal box should be sufficient. Be sure the box is secure, the wires is clamped in the box and the caps are left on. As an extra measurement you could even cap them and then run electrical tape around them to ensure the caps won't fall off. Be sure to put a cover over the box when all done. Writing on the cover of what it is can't hurt either. If it is on its own circuit you could even turn the breaker off after this and label in the breaker as well.
add a comment |
Sounds like you don't want the wire.
First figure out which breaker that circuit is on.
Turn off the breaker, see what other things go off. Put a harmonic tracer on the wire, find where it junctions and disconnect it there.
Typically fanhoods are on a circuit with other items. Once you have it disconnected in the box you could cut it back to the knock out and push it through so it could never be energized again then you could cut the wire in the cabinet back to where it penetrates the cabinet.
Or go with your plan put a box with a cover and wire nuts and leave it live.
add a comment |
Meeting your request for safety, and ranked best to worst:
Trip and remove the breaker, replacing it with an appropriate position plug (other circuits may be on the breaker, preventing this).
Disconnect the wire from wherever it goes (the breaker, an outlet, etc.) and pull it out (it may be stapled, preventing this).
(After temporarily tripping breaker): Thread wire into a junction box with a stress-relief connector. Position the box as close to the hole in the wall as possible. Re-cap the wires, wrap with electrical tape. Screw to the wall and affix face plate.
(After temporarily tripping breaker): Wrap a few turns around the wire nuts with electrical wire, then wrap the entire NM from where the outer insulation was stripped away to and including the wire nuts.
As others have mentioned, there isn't a code-happy solution here. However, solutions (1)-(3) will pass a home inspection when you sell the home. (4) might not. It will depend on the inspector.
add a comment |
Your Answer
StackExchange.ready(function()
var channelOptions =
tags: "".split(" "),
id: "73"
;
initTagRenderer("".split(" "), "".split(" "), channelOptions);
StackExchange.using("externalEditor", function()
// Have to fire editor after snippets, if snippets enabled
if (StackExchange.settings.snippets.snippetsEnabled)
StackExchange.using("snippets", function()
createEditor();
);
else
createEditor();
);
function createEditor()
StackExchange.prepareEditor(
heartbeatType: 'answer',
autoActivateHeartbeat: false,
convertImagesToLinks: false,
noModals: true,
showLowRepImageUploadWarning: true,
reputationToPostImages: null,
bindNavPrevention: true,
postfix: "",
imageUploader:
brandingHtml: "Powered by u003ca class="icon-imgur-white" href="https://imgur.com/"u003eu003c/au003e",
contentPolicyHtml: "User contributions licensed under u003ca href="https://creativecommons.org/licenses/by-sa/3.0/"u003ecc by-sa 3.0 with attribution requiredu003c/au003e u003ca href="https://stackoverflow.com/legal/content-policy"u003e(content policy)u003c/au003e",
allowUrls: true
,
noCode: true, onDemand: true,
discardSelector: ".discard-answer"
,immediatelyShowMarkdownHelp:true
);
);
BradDaBug is a new contributor. Be nice, and check out our Code of Conduct.
Sign up or log in
StackExchange.ready(function ()
StackExchange.helpers.onClickDraftSave('#login-link');
);
Sign up using Google
Sign up using Facebook
Sign up using Email and Password
Post as a guest
Required, but never shown
StackExchange.ready(
function ()
StackExchange.openid.initPostLogin('.new-post-login', 'https%3a%2f%2fdiy.stackexchange.com%2fquestions%2f162263%2fhow-do-i-make-this-wiring-inside-cabinet-safer-pic%23new-answer', 'question_page');
);
Post as a guest
Required, but never shown
4 Answers
4
active
oldest
votes
4 Answers
4
active
oldest
votes
active
oldest
votes
active
oldest
votes
There is nothing you can do with old wiring that doesn't meet code that will make it meet code. Old NM cable with no ground may have been "grandfathered" into an existing building, so long as you don't alter it. But that would not apply here because the WAY it was done was never per code.
Do you really need a circuit there? I would just find out where it comes from and disconnect it there, then pull it out. If you DO want another circuit there, you can attach new NM cable with a ground to the end of this before pulling it out, then get an "old work box" that can be mounted into the wall properly. An old work box is designed to go into a cut-out in the wall, then has "molly bolt" type fasteners that turn behind the wall and snug up against the back of it to hold the box in place (make sure you put the wire through the KO first!). Once the wire is in there, you can put in a receptacle for a light, fan etc.
2
If it's stapled anywhere it probably won't pull.
– J...
5 hours ago
True, but given that the original installer didn't seem to have any regard for doing things right, it's likely not stapled anywhere either!
– J. Raefield
4 hours ago
3
Whomever moved the stove and removed the old fixture made a mess, but the wire is probably original and fastened if it is.
– J...
4 hours ago
add a comment |
There is nothing you can do with old wiring that doesn't meet code that will make it meet code. Old NM cable with no ground may have been "grandfathered" into an existing building, so long as you don't alter it. But that would not apply here because the WAY it was done was never per code.
Do you really need a circuit there? I would just find out where it comes from and disconnect it there, then pull it out. If you DO want another circuit there, you can attach new NM cable with a ground to the end of this before pulling it out, then get an "old work box" that can be mounted into the wall properly. An old work box is designed to go into a cut-out in the wall, then has "molly bolt" type fasteners that turn behind the wall and snug up against the back of it to hold the box in place (make sure you put the wire through the KO first!). Once the wire is in there, you can put in a receptacle for a light, fan etc.
2
If it's stapled anywhere it probably won't pull.
– J...
5 hours ago
True, but given that the original installer didn't seem to have any regard for doing things right, it's likely not stapled anywhere either!
– J. Raefield
4 hours ago
3
Whomever moved the stove and removed the old fixture made a mess, but the wire is probably original and fastened if it is.
– J...
4 hours ago
add a comment |
There is nothing you can do with old wiring that doesn't meet code that will make it meet code. Old NM cable with no ground may have been "grandfathered" into an existing building, so long as you don't alter it. But that would not apply here because the WAY it was done was never per code.
Do you really need a circuit there? I would just find out where it comes from and disconnect it there, then pull it out. If you DO want another circuit there, you can attach new NM cable with a ground to the end of this before pulling it out, then get an "old work box" that can be mounted into the wall properly. An old work box is designed to go into a cut-out in the wall, then has "molly bolt" type fasteners that turn behind the wall and snug up against the back of it to hold the box in place (make sure you put the wire through the KO first!). Once the wire is in there, you can put in a receptacle for a light, fan etc.
There is nothing you can do with old wiring that doesn't meet code that will make it meet code. Old NM cable with no ground may have been "grandfathered" into an existing building, so long as you don't alter it. But that would not apply here because the WAY it was done was never per code.
Do you really need a circuit there? I would just find out where it comes from and disconnect it there, then pull it out. If you DO want another circuit there, you can attach new NM cable with a ground to the end of this before pulling it out, then get an "old work box" that can be mounted into the wall properly. An old work box is designed to go into a cut-out in the wall, then has "molly bolt" type fasteners that turn behind the wall and snug up against the back of it to hold the box in place (make sure you put the wire through the KO first!). Once the wire is in there, you can put in a receptacle for a light, fan etc.
answered 11 hours ago
J. RaefieldJ. Raefield
3,869210
3,869210
2
If it's stapled anywhere it probably won't pull.
– J...
5 hours ago
True, but given that the original installer didn't seem to have any regard for doing things right, it's likely not stapled anywhere either!
– J. Raefield
4 hours ago
3
Whomever moved the stove and removed the old fixture made a mess, but the wire is probably original and fastened if it is.
– J...
4 hours ago
add a comment |
2
If it's stapled anywhere it probably won't pull.
– J...
5 hours ago
True, but given that the original installer didn't seem to have any regard for doing things right, it's likely not stapled anywhere either!
– J. Raefield
4 hours ago
3
Whomever moved the stove and removed the old fixture made a mess, but the wire is probably original and fastened if it is.
– J...
4 hours ago
2
2
If it's stapled anywhere it probably won't pull.
– J...
5 hours ago
If it's stapled anywhere it probably won't pull.
– J...
5 hours ago
True, but given that the original installer didn't seem to have any regard for doing things right, it's likely not stapled anywhere either!
– J. Raefield
4 hours ago
True, but given that the original installer didn't seem to have any regard for doing things right, it's likely not stapled anywhere either!
– J. Raefield
4 hours ago
3
3
Whomever moved the stove and removed the old fixture made a mess, but the wire is probably original and fastened if it is.
– J...
4 hours ago
Whomever moved the stove and removed the old fixture made a mess, but the wire is probably original and fastened if it is.
– J...
4 hours ago
add a comment |
You may want to find what the local code says about such and follow it. I think just putting it "properly" in a metal box should be sufficient. Be sure the box is secure, the wires is clamped in the box and the caps are left on. As an extra measurement you could even cap them and then run electrical tape around them to ensure the caps won't fall off. Be sure to put a cover over the box when all done. Writing on the cover of what it is can't hurt either. If it is on its own circuit you could even turn the breaker off after this and label in the breaker as well.
add a comment |
You may want to find what the local code says about such and follow it. I think just putting it "properly" in a metal box should be sufficient. Be sure the box is secure, the wires is clamped in the box and the caps are left on. As an extra measurement you could even cap them and then run electrical tape around them to ensure the caps won't fall off. Be sure to put a cover over the box when all done. Writing on the cover of what it is can't hurt either. If it is on its own circuit you could even turn the breaker off after this and label in the breaker as well.
add a comment |
You may want to find what the local code says about such and follow it. I think just putting it "properly" in a metal box should be sufficient. Be sure the box is secure, the wires is clamped in the box and the caps are left on. As an extra measurement you could even cap them and then run electrical tape around them to ensure the caps won't fall off. Be sure to put a cover over the box when all done. Writing on the cover of what it is can't hurt either. If it is on its own circuit you could even turn the breaker off after this and label in the breaker as well.
You may want to find what the local code says about such and follow it. I think just putting it "properly" in a metal box should be sufficient. Be sure the box is secure, the wires is clamped in the box and the caps are left on. As an extra measurement you could even cap them and then run electrical tape around them to ensure the caps won't fall off. Be sure to put a cover over the box when all done. Writing on the cover of what it is can't hurt either. If it is on its own circuit you could even turn the breaker off after this and label in the breaker as well.
answered 9 hours ago
Micah MontoyaMicah Montoya
58116
58116
add a comment |
add a comment |
Sounds like you don't want the wire.
First figure out which breaker that circuit is on.
Turn off the breaker, see what other things go off. Put a harmonic tracer on the wire, find where it junctions and disconnect it there.
Typically fanhoods are on a circuit with other items. Once you have it disconnected in the box you could cut it back to the knock out and push it through so it could never be energized again then you could cut the wire in the cabinet back to where it penetrates the cabinet.
Or go with your plan put a box with a cover and wire nuts and leave it live.
add a comment |
Sounds like you don't want the wire.
First figure out which breaker that circuit is on.
Turn off the breaker, see what other things go off. Put a harmonic tracer on the wire, find where it junctions and disconnect it there.
Typically fanhoods are on a circuit with other items. Once you have it disconnected in the box you could cut it back to the knock out and push it through so it could never be energized again then you could cut the wire in the cabinet back to where it penetrates the cabinet.
Or go with your plan put a box with a cover and wire nuts and leave it live.
add a comment |
Sounds like you don't want the wire.
First figure out which breaker that circuit is on.
Turn off the breaker, see what other things go off. Put a harmonic tracer on the wire, find where it junctions and disconnect it there.
Typically fanhoods are on a circuit with other items. Once you have it disconnected in the box you could cut it back to the knock out and push it through so it could never be energized again then you could cut the wire in the cabinet back to where it penetrates the cabinet.
Or go with your plan put a box with a cover and wire nuts and leave it live.
Sounds like you don't want the wire.
First figure out which breaker that circuit is on.
Turn off the breaker, see what other things go off. Put a harmonic tracer on the wire, find where it junctions and disconnect it there.
Typically fanhoods are on a circuit with other items. Once you have it disconnected in the box you could cut it back to the knock out and push it through so it could never be energized again then you could cut the wire in the cabinet back to where it penetrates the cabinet.
Or go with your plan put a box with a cover and wire nuts and leave it live.
answered 10 hours ago
Fresh CodemongerFresh Codemonger
4417
4417
add a comment |
add a comment |
Meeting your request for safety, and ranked best to worst:
Trip and remove the breaker, replacing it with an appropriate position plug (other circuits may be on the breaker, preventing this).
Disconnect the wire from wherever it goes (the breaker, an outlet, etc.) and pull it out (it may be stapled, preventing this).
(After temporarily tripping breaker): Thread wire into a junction box with a stress-relief connector. Position the box as close to the hole in the wall as possible. Re-cap the wires, wrap with electrical tape. Screw to the wall and affix face plate.
(After temporarily tripping breaker): Wrap a few turns around the wire nuts with electrical wire, then wrap the entire NM from where the outer insulation was stripped away to and including the wire nuts.
As others have mentioned, there isn't a code-happy solution here. However, solutions (1)-(3) will pass a home inspection when you sell the home. (4) might not. It will depend on the inspector.
add a comment |
Meeting your request for safety, and ranked best to worst:
Trip and remove the breaker, replacing it with an appropriate position plug (other circuits may be on the breaker, preventing this).
Disconnect the wire from wherever it goes (the breaker, an outlet, etc.) and pull it out (it may be stapled, preventing this).
(After temporarily tripping breaker): Thread wire into a junction box with a stress-relief connector. Position the box as close to the hole in the wall as possible. Re-cap the wires, wrap with electrical tape. Screw to the wall and affix face plate.
(After temporarily tripping breaker): Wrap a few turns around the wire nuts with electrical wire, then wrap the entire NM from where the outer insulation was stripped away to and including the wire nuts.
As others have mentioned, there isn't a code-happy solution here. However, solutions (1)-(3) will pass a home inspection when you sell the home. (4) might not. It will depend on the inspector.
add a comment |
Meeting your request for safety, and ranked best to worst:
Trip and remove the breaker, replacing it with an appropriate position plug (other circuits may be on the breaker, preventing this).
Disconnect the wire from wherever it goes (the breaker, an outlet, etc.) and pull it out (it may be stapled, preventing this).
(After temporarily tripping breaker): Thread wire into a junction box with a stress-relief connector. Position the box as close to the hole in the wall as possible. Re-cap the wires, wrap with electrical tape. Screw to the wall and affix face plate.
(After temporarily tripping breaker): Wrap a few turns around the wire nuts with electrical wire, then wrap the entire NM from where the outer insulation was stripped away to and including the wire nuts.
As others have mentioned, there isn't a code-happy solution here. However, solutions (1)-(3) will pass a home inspection when you sell the home. (4) might not. It will depend on the inspector.
Meeting your request for safety, and ranked best to worst:
Trip and remove the breaker, replacing it with an appropriate position plug (other circuits may be on the breaker, preventing this).
Disconnect the wire from wherever it goes (the breaker, an outlet, etc.) and pull it out (it may be stapled, preventing this).
(After temporarily tripping breaker): Thread wire into a junction box with a stress-relief connector. Position the box as close to the hole in the wall as possible. Re-cap the wires, wrap with electrical tape. Screw to the wall and affix face plate.
(After temporarily tripping breaker): Wrap a few turns around the wire nuts with electrical wire, then wrap the entire NM from where the outer insulation was stripped away to and including the wire nuts.
As others have mentioned, there isn't a code-happy solution here. However, solutions (1)-(3) will pass a home inspection when you sell the home. (4) might not. It will depend on the inspector.
answered 24 mins ago
JBHJBH
25528
25528
add a comment |
add a comment |
BradDaBug is a new contributor. Be nice, and check out our Code of Conduct.
BradDaBug is a new contributor. Be nice, and check out our Code of Conduct.
BradDaBug is a new contributor. Be nice, and check out our Code of Conduct.
BradDaBug is a new contributor. Be nice, and check out our Code of Conduct.
Thanks for contributing an answer to Home Improvement Stack Exchange!
- Please be sure to answer the question. Provide details and share your research!
But avoid …
- Asking for help, clarification, or responding to other answers.
- Making statements based on opinion; back them up with references or personal experience.
To learn more, see our tips on writing great answers.
Sign up or log in
StackExchange.ready(function ()
StackExchange.helpers.onClickDraftSave('#login-link');
);
Sign up using Google
Sign up using Facebook
Sign up using Email and Password
Post as a guest
Required, but never shown
StackExchange.ready(
function ()
StackExchange.openid.initPostLogin('.new-post-login', 'https%3a%2f%2fdiy.stackexchange.com%2fquestions%2f162263%2fhow-do-i-make-this-wiring-inside-cabinet-safer-pic%23new-answer', 'question_page');
);
Post as a guest
Required, but never shown
Sign up or log in
StackExchange.ready(function ()
StackExchange.helpers.onClickDraftSave('#login-link');
);
Sign up using Google
Sign up using Facebook
Sign up using Email and Password
Post as a guest
Required, but never shown
Sign up or log in
StackExchange.ready(function ()
StackExchange.helpers.onClickDraftSave('#login-link');
);
Sign up using Google
Sign up using Facebook
Sign up using Email and Password
Post as a guest
Required, but never shown
Sign up or log in
StackExchange.ready(function ()
StackExchange.helpers.onClickDraftSave('#login-link');
);
Sign up using Google
Sign up using Facebook
Sign up using Email and Password
Sign up using Google
Sign up using Facebook
Sign up using Email and Password
Post as a guest
Required, but never shown
Required, but never shown
Required, but never shown
Required, but never shown
Required, but never shown
Required, but never shown
Required, but never shown
Required, but never shown
Required, but never shown
1
Is your goal to just leave those wires in the cabinet unused, but in a safe manner - or would you like to utilize them for the light fixture again?
– PhilippNagel
9 hours ago
1
@PhilippNagel I'd like to put the light fixture back, but it's not absolutely critical.
– BradDaBug
9 hours ago